Fire curtain furnace testing

Compliance

Compliance built into every product

Fire doors tested to IS 3614:2021 at CBRI, and fire curtains tested to EN 1634-1, EN 12101-1 and EN 15269-11, independently verified by Efectis and TÜV SÜD.

Certifications & Testing Standards

ISO

ISO Certified

Quality management systems for manufacturing excellence

Efectis

Efectis Tested

Independent fire testing at Efectis laboratory, Turkey

CE Mark

EN Tested

Tested and classified to European fire curtain standards

TÜV SÜD

TÜV SÜD Verified

Third-party verification of product performance

MSME

MSME Registered

Recognised Indian manufacturing enterprise

• Assurance

Certified to Indian and European standards

CBRI Tested

Every BÖLDT fire door is tested at CBRI (Central Building Research Institute) and NABL-accredited laboratories.

IS 3614:2021

Fire doors tested to IS 3614:2021. BIS licence number available on request.

NBCS 2026 Compliant

Products and installation guidance aligned to the National Building Construction Standards 2026 (SP 7:2026), Part F - Fire and Life Safety, which supersedes NBC 2016.

EN Tested (Fire Curtains)

Fire and smoke curtains tested and classified to EN 1634-1, EN 12101-1 and EN 15269-11. CE marking and Declaration of Performance available on request. Independently verified by Efectis and TÜV SÜD.

• NBCS 2026

National Building Construction Standards 2026, Part F

NBCS 2026 (SP 7:2026) replaced NBC 2016 in April 2026. The following clauses are quoted directly from the published standard.

Part F, Clause 2.22, Note 2

On mandatory exit protection

“Fire doors in exits should have fire rating as required in this Part to meet the requirement of integrity and stability; and the minimum insulation criteria should be 30 min.”

Part F, Clause 2.24

On firefighting shafts

“An enclosed shaft having a protected area of 120 min fire resistance rating comprising a protected lobby, staircase, and fireman's lift... The firefighting shaft should be equipped with 120 min fire doors.”

Part F, Clause 3.5.4.6

On vertical openings and compartmentation

“Every vertical opening between the floors of a building should be suitably enclosed or protected, as necessary, to provide reasonable safety to the occupants... and limitation of damage to the building and its contents.”

Minimum ratings by location, NBCS 2026

Location / RequirementMinimum RatingNBCS 2026 Clause
Single-staircase building - lobby / stairwell120 min (lobby) / 60 min (stairwell)Cl. 1.2, Note 2
Firefighting shaft (lobby, staircase, fireman's lift)120 minCl. 2.24
Non-naturally ventilated (pressurised) areas - lift lobby & stairwell entrances120 minCl. 4.2.7
Basement access from occupied floors above (car parking)120 minCl. 4.2.19.4
Lift lobby at all levels, pressurised 25–30 Pa120 minTable 5, Cl. 4.4.2.5(b)
Horizontal exit doorway between compartments120 minCl. 2.40, Annex D-4.1
Guest room corridors / sleeping accommodation exit corridors30 min (door) / 60 min (wall)Cl. 4.5.3.3
Fire separating walls (industrial, non-hazardous zones)120 minCl. 6.7.1.1
Openings within 3 m of a fire separating wall60 minCl. 6.7.1.1(g)
Type 4 construction - fire separating walls/floors120 minCl. 3.5.4.3

• Ratings

Fire resistance rating scale

30 min

Guest room corridors, sleeping areas

60 min

Fire separating walls, stairwells

120 min

Firefighting shafts, lift lobbies, basements

240 min

Automatic fire curtains, high-hazard zones

• Fire curtains

Fire curtain performance types, NBCS 2026 + EN standards

NBCS 2026, Clause 4.5.2.1, sets out three fire curtain performance types directly, requiring third-party certification for each. BÖLDT curtains meet these parameters and additionally carry EN certification for international specifiers.

E

Integrity

Resists flame and hot gas passage, 120 min

EW

Radiation control

Heat transfer capped at 15 kW/m² at 1 m

EI

Insulation

Limits far-face temperature rise, +140°C max

Sa

Smoke control

Leakage capped at 3 m³/m/h at 25 Pa

EN 1634-1

Fire Resistance of Door and Shutter Assemblies

Governs fire resistance testing of door sets, shutter assemblies and openable windows - including fire curtain systems. Curtains are evaluated on their ability to maintain integrity and control fire and smoke spread across openings for defined periods.

EN 12101-1

Smoke and Heat Control Systems

Defines performance requirements for smoke and heat control systems in buildings. Curtains tested to EN 12101-1 demonstrate measurable performance in real fire scenarios, supporting life safety strategy and regulatory compliance.

EN 15269-11

Extended Application of Fire Resistance Test Results - Curtain Assemblies

Provides the framework for extending fire test results across a defined range of curtain sizes, widths and installation conditions, rather than requiring independent testing for every configuration.

EN 13501

Fire Classification of Construction Products

Translates fire test results into clearly defined performance ratings - integrity (E), radiation (W) and insulation (I) - giving specifiers, consultants and authorities a transparent, universally understood classification.

Curtain type restrictions by building occupancy, Table 6, NBCS 2026 (Cl. 4.5.3)

Building TypeRestriction
Enclosed basement vehicle parkingType 2 only, limited to driveways ≤ 9 m
Hospitals / nursing homes (with beds/sleeping patients)Type 3 only
Buildings for custody/care of children, aged, incapable personsType 3 only
Mercantile buildings / department stores / marketsType 2 only
Assembly buildings (with/without atriums)Type 2 only
Business occupancy buildingsType 1 only
Datacentre buildingsType C only (fire-rated glazed partition/door, not fabric)
Hotel buildings (with or without dining facilities)Type C only (fire-rated glazed partition/door, not fabric)

Have a specific compliance question?

Our technical team can walk you through the applicable NBCS clauses and EN standards for your project.